Description
A demand water pump can only run flat-out or off — its pressure switch snaps on and off — so for a small draw like a dribbling tap it short-cycles: rapid on/off bursts that are noisy, wear out the pump and pressure switch, and give a pulsing flow. A Johnson accumulator tank fixes this. Behind a captive air charge it stores a cushion of pressurised water; when you crack a tap the stored water is delivered without the pump starting, and the pump only runs to refill the tank. The result is fewer pump starts, steady even pressure, a quieter system and far longer pump and switch life — and it soaks up pulsation and water-hammer as a bonus.
Why it’s required
Every standard demand pump — the Aqua Jet WPS and the compact Aqua Jet — benefits from an accumulator; without one they cycle hard on small draws. (The variable-speed Flow Master smooths flow electronically and does not need one.)
Where to install
Fit the accumulator on the pressure (outlet) side of the pump, as close to the pump as practical, tee’d into the delivery line. Support the tank on a bracket so its weight isn’t hanging on the plumbing, and keep the air valve accessible. The 2 L and 5 L tanks mount on a bracket with a short hose to a tee; the 1/2″ in-line unit tees straight into the pipe where space is tight.
Setting and maintaining the air charge
The captive air charge does the work, and it is the one thing to maintain. Johnson tanks ship pre-charged at about 0.8 bar (12 psi), but for best results set the pre-charge to roughly 2–3 psi below your pump’s cut-in pressure — too high and the tank won’t take water, too low and it does little.
To set or check it — always with the system depressurised:
- Switch the pump off.
- Open a tap and let all water pressure bleed off.
- Check the Schrader air valve (like a tyre valve) with a low-pressure gauge.
- Add air with a hand or bicycle pump to the target — never with the system pressurised.
- Close the tap and restore power.
Re-check every 6–12 months, or whenever the pump starts short-cycling again — air slowly permeates out over time.
Troubleshooting
- Pump still short-cycles — the air charge has bled down; re-charge it. If it won’t hold, the diaphragm has failed (below).
- Water at the Schrader valve — the internal diaphragm/bladder has ruptured (air and water have mixed). It can’t be repaired — replace the tank.
- Waterlogged / no cushion — lost pre-charge; re-charge, or replace if the diaphragm is gone.
- Pulsing at the taps or water-hammer — pre-charge set wrong, or the tank is undersized for the system; correct the charge or step up a size.
Choosing the size
Bigger tanks store more water, so the pump cycles even less. As a guide: the 2 L suits small one- to two-outlet systems; the 5 L gives a bigger buffer for multi-outlet systems and the quietest, least-cycling result; the 1/2″ in-line unit is the compact choice that tees straight into the pipe where there’s no room for a bracket-mounted tank.
Key features
- Smooths pressure and cuts pump cycling — quieter system, longer pump life
- Captive air charge with adjustable Schrader valve; factory pre-charged ~12 psi
- Absorbs pulsation and water-hammer
- 2 L, 5 L, or compact 1/2″ in-line
- Corrosion-resistant; suits Johnson and compatible demand-pump systems
Johnson Pump Marine by SPX FLOW. Supplied by Y3 Marine.